AIR-CONDITIONING REFRIGERATION PLANTS WITH ICE STORAGE
IN HOTELS IN SPAIN AND PORTUGAL. DESIGN AND ECONOMIC ANALYSIS
|
Celestino R. Ruivo1,
José M. Pinazo2
and Angel Barragán2
1 Área Departamental de Engenharia Mecânica,
Escola Superior de Tecnologia da Universidade do Algarve - Campus da
Penha, 8000 Faro, Portugal (cruivo@ualg.pt)
2 Departamento de Termodinamica Aplicada, Universidad Politécnica de
Valencia , España
(jmpinazo@ter.upv.es), (anbarcer@doctor.upv.es)
Abstract :
The cooling needs in hotels, like in a lot of buildings, are usually
high during the day when the price of electricity is high.
The integration of a thermal storage system in a HVAC refrigeration
plant can be advantageous, because the storage system can be charged
at night, with the chiller running at maximum capacity with low
electric energy costs. The other main advantage is due to the possible
reduction of electric power that one needs in the refrigeration plant.
This change in the electricity consumption, the reduction of the
consumption during times expensive electricity price and the increase
in usage during low cost periods of electricity, is also advantageous
for to the electricity production and distribution companies because
the consumption is more stable.
When designing a refrigeration plant with an ice bank for air
conditioning purposes, for example in a hotel, it is first necessary
to estimate the cooling needs considering an adequate scenario for
design purposes and a realistic scenario for energy consumption. The
histogram showing cooling needs on an hourly basis over several days,
for example a typical day each month, must be considered in order to
size the refrigeration plant, chiller and the ice bank.
This work presents some results of a case study of two similar hotels
situated in South Spain and South Portugal respectively. The cooling
loads in several zones of the building are calculated with the program
"DPClima". Then, using the program SIPfrio, first the
refrigeration loads of the central plant are estimated, and then the
preliminary sizing of the refrigeration plant imposing an adequate
storage strategy is estimated and next the preliminary sizing by
dynamic simulation processes is confirmed or rectified. At the end,
the economic analysis is done considering a realistic scenario for
energy cooling needs.
Résumé :
Les besoins de refroidissement des hôtels, et plus généralement
dans tout type de bâtiment, sont élevés quand le prix de
l'électricité est aussi plus élevé.
L'intégration des systèmes de stockage de froid dans les
installations de climatisation permet tout d'abord de faire
fonctionner le groupe frigorifique à pleine charge la nuit, c'est à
dire lorsque l'électricité est bon marché. Ceci permet également
de réduire la puissance à installer
Le déplacement de la consommation d'électricité obtenue intéresse
aussi les entreprises de production et de distribution de l'énergie
électrique.
Quand on fait le dimensionnement d'une installation de climatisation
avec stockage de glace, par exemple dans un hôtel, il faut faire deux
estimations de la charge thermique de refroidissement, une est valable
pour dimensionner les équipements et l'autre pour faire les analyses
de consommation d'énergie et économique. On doit pour cela considérer
des histogrammes de charge sur une base horaire.
Dans ce travail on présente des résultats d'une étude considérant
deux hôtels identiques, un au Portugal et l'autre en Espagne. Les
charges thermiques des différentes zones sont estimées par le
logiciel "DPClima". Le logiciel SIPFRIO permet ensuite de
calculer les besoins frigorifiques réels de l'installation de
climatisation pour pré-dimensionner l'installation, en intégrant le
scénario de stockage. La simulation dynamique permet alors de
confirmer et d’optimiser le dimensionnement et la stratégie de
stockage/déstockage, puis d’effectuer l’analyse économique sur
des bases réalistes.
Keywords : Refrigeration Plants, Ice Banks, Storage Strategies, Dynamic
Simulation, Economic Analysis
|
|
|
Chih Wu
7 september
11h40
(Abstract 85)
|
INTELLIGENT COMPUTER AIDED DESIGN, ANALYSIS AND
IMPROVEMENT OF COOLING, REFRIGERATION, HEATING AND POWER GENERATING SYSTEMS |
Chih Wu
Department of Mechanical Engineering, U.S. Naval Academy, Annapolis, MD 21402, USA
The design and analysis of cooling, refrigeration,
heating and power generating systems are long and tedious. It is very
necessary to obtain the cycle performance quickly and accurately. This
paper describes the use of an intelligent computer aided software in
design, analysis and possible refinements of these systems. Objectives
for improvements, constraints, and consequently design, which cannot be
easily accomplished from the conventional way, are emphasized. Using the
software increases engineers interest and design ability in these
systems.
Usually when cooling, refrigeration, heating and
power generating systems are designed and analyzed using the tradition
way, much time is required for table or chart searching and calculations.
As the computer become more available and sophisticated, various
researchers have tried to solve this problem in order to save time. A
software which is fast, flexible, intelligent and easy to use is
necessary.
An ICAI (Intelligent Computer-Aided Instruction)
software called CyclePad is developed to help with the conceptual design
and analysis of thermodynamic cycles. CyclePad works in three (design,
analysis and contradiction) modes. In the design mode, a graphical
editor is used to place components taken from the inventory shop and
connect them. When CyclePad is satisfied that the structure is fully
laid out, the user can proceed to the analysis mode. In the analysis
mode, the working fluid and modeling of each component are specified,
and numerical values for the properties of components are then entered
by the user. As soon as this information are provided, all performance
characteristics of the system are displayed. A sensitivity analysis is
also available in the CyclePad. An important aspect of carrying out an
analysis is to check whether or not the results are physically
meaningful. In such a case, CyclePad can use its intelligent knowledge
to detect the conflict similar to a senior engineer catching junior
engineer mistakes and enters the contradiction mode. CyclePad also has a
coaching facility which allows the user to determine which of his
assumptions contradicate to each other and why.
|
|
|
R. Gicquel
7 september
12h00
(Abstract 88)
|
OPTIMISATION DU CYCLE EAU-VAPEUR D'UNE CENTRALE IGCC
|
R. Gicquel,
M. Williams, Ecole des Mines de Paris
K. Aubert, Electricité de France
Avec l'apparition de nouvelles générations de
centrales électriques à haut rendement et fortement intégrées,
l'optimisation poussée du design des réseaux d'échangeurs devient une
nécessité. Les techniques d'optimisation systémique, fondées sur
l'intégration thermique, permettent de répondre à ce problème,
particulièrement sensible dans le cas des nouveaux cycles IGCC (Cycle
combiné à gazéification intégrée) d'une grande complexité puisque
tous les sous-systèmes (gazéification, traitement du gaz,
séparation d'air, cycle combiné) sont couplés via le réseau
eau-vapeur.
La méthode utilisée est l'extension au cas des
centrales de production d'électricité ou de cogénération de la
méthode du Pincement développée dans le cadre du génie chimique pour
optimiser la configuration de très gros réseaux d'échangeurs (comme
par exemple ceux d'une raffinerie).
Elle est implémentée dans le progiciel THERMOPTIM (http://www.thermoptim.com),
qui fournit un environnement de modélisation muni d'un éditeur
graphique, où les fonctions de simulation et la méthode d'optimisation
sont profondément interconnectées, afin de pouvoir facilement faire
varier l'ensemble des paramètres caractéristiques du système
étudié. Une étude a posteriori du design du circuit eau-vapeur de la
centrale IGCC de Puertollano a été effectuée. Elle a permis
d'identifier les paramètres critiques du cycle et de proposer des
modifications pour optimiser la puissance électrique fournie en
respectant les contraintes existantes.
Cette méthode intéresse EdF, non pour se substituer
aux constructeurs, mais pour avoir la capacité de valider leurs
propositions et d'améliorer le design le cas échéant.
|
|
|
D. Mugnier
7 september
12h20
(Abstract 13)
|
MODELLING AND SIZING OF AN ABSORPTION SOLAR COOLING
SYSTEM FOR AN OFFICE BUILDING APPLICATION
|
Daniel Mugnier1a, Vincent Goetz1,
Jean-Yves Quinette2,
François Neirac3,
Bruno Gagnepain4
1 I.M.P C.N.R.S, Site Carnot, rambla de la thermodynamique, TECNOSUD, 66860 Perpignan, France
2 TECSOL S.A, 105 av. Alfred Kastler, BP 434, TECNOSUD, 66004 Perpignan cedex, France
3 C.E.N.E.R.G, E.N.S.M.P, rue Claude Daunesse, BP 207, 06904 Sophia Antipolis cedex, France
4 ADEME, 500 route des Lucioles, 06560 Sophia-Antipolis cedex, France
This paper is dedicated to describe a modular method aimed at sizing
an absorption solar cooling system. Such a system is intended to an
office building application in South of France. Thanks to a TRNSYS
simulation of the building in a first part and of the global system in a
second part, different kind and area of solar collectors are tested
(flat plate and evacuated tube collectors). Comfortable indoor
conditions, taken from the German standard DIN 1946, must be respected
as much as possible. To measure the level of respect, the number of
hours exceeding a limit (in correlation with the standard) is counted.
The addition of a hot water storage into the system reveals to be very
interesting. If a strict respect of comfortable indoor conditions is
required, the gas burner back up solution is then the best solution.
Such a method based on simulation series can be generalised on other
solar cooling projects with different building and meteorological data.
|